Trisha Shetty (Editor)

Sick building syndrome

Updated on
Edit
Like
Comment
Share on FacebookTweet on TwitterShare on LinkedInShare on Reddit

Sick building syndrome (SBS) is a phenomenon affecting building occupants who claim to experience acute health and comfort effects that appear to be linked to time spent in a building, but where no specific illness or cause can be identified. SBS is also used interchangeably with "building-related symptoms", which orients the name of the condition around patients rather than a "sick" building. A 1984 World Health Organization (WHO) report suggested up to 30% of new and remodeled buildings worldwide may be subject of complaints related to poor indoor air quality.

Contents

Sick building causes are frequently pinned down to flaws in the heating, ventilation, and air conditioning (HVAC) systems. Other causes have been attributed to contaminants produced by outgassing of some types of building materials, volatile organic compounds (VOC), molds (see mold health issues), improper exhaust ventilation of ozone (byproduct of some office machinery), light industrial chemicals used within, or lack of adequate fresh-air intake/air filtration (see Minimum efficiency reporting value).

Symptoms

Human exposure to bioaerosols has been documented to give rise to a variety of adverse health effects. Building occupants complain of symptoms such as sensory irritation of the eyes, nose, throat; neurotoxic or general health problems; skin irritation; nonspecific hypersensitivity reactions; infectious diseases; and odor and taste sensations.

Extrinsic allergic alveolitis has been associated with the presence of fungi and bacteria in the moist air of residential houses and commercial offices.

The WHO has classified the reported symptoms into broad categories, including: mucous membrane irritation (eye, nose, and throat irritation), neurotoxic effects (headaches, fatigue, and irritability), asthma and asthma-like symptoms (chest tightness and wheezing), skin dryness and irritation, gastrointestinal complaints and more.

Several sick occupants may report individual symptoms which do not appear to be connected. The key to discovery is the increased incidence of illnesses in general with onset or exacerbation within a fairly close time frame—usually within a period of weeks. In most cases, SBS symptoms will be relieved soon after the occupants leave the particular room or zone. However, there can be lingering effects of various neurotoxins, which may not clear up when the occupant leaves the building. In some cases—particularly in sensitive individuals—there can be long-term health effects.

Psychological factors

One study looked at commercial buildings and their employees, comparing some environmental factors suspected of inducing SBS to a self-reported survey of the occupants, finding that the measured psycho-social circumstances appeared more influential than the tested environmental factors. The list of environmental factors in the study can be found here. Limitations of the study include that it only measured the indoor environment of commercial buildings, which have different building codes than residential buildings, and that the assessment of building environment was based on layman observation of a limited number of factors.

Research has shown that SBS shares several symptoms common in other conditions thought to be at least partially caused by psychosomatic tendencies. The umbrella term 'autoimmune/inflammatory syndrome induced by adjuvants' has been suggested. Other members of the suggested group include Silicosis, Macrophagic myofascitis, The Gulf War syndrome, Post-vaccination phenomena.

Workplace

Greater effects were found with features of the psychosocial work environment including high job demands and low support. The report concluded that the physical environment of office buildings appears to be less important than features of the psychosocial work environment in explaining differences in the prevalence of symptoms. However, there is still a relationship between sick building syndrome and symptoms of workers regardless of workplace stress.

Excessive work stress or dissatisfaction, poor interpersonal relationships and poor communication are often seen to be associated with SBS, recent studies show that a combination of environmental sensitivity and stress can greatly contribute to sick building syndrome.

Specific work-related stressors are related with specific SBS symptoms. Workload and work conflict are significantly associated with general symptoms (headache, abnormal tiredness, sensation of cold or nausea). While crowded workspaces and low work satisfaction are associated with upper respiratory symptoms.

Engineers are often effected by Sick building syndome. A commonly studied case is Stephen Danielson. He commonly has the ailment for 6 months out of the year. It manifests as a wheeze. More commonly known as the Danielson Wheeze.

Specific careers are also associated with specific SBS symptoms. Transport, communication, healthcare, and social workers have highest prevalence of general symptoms. Skin symptoms such as eczema, itching, and rashes on hands and face are associated with technical work. Forestry, agriculture, and sales workers have the lowest rates of sick building syndrome symptoms.

Milton et al. determined the cost of sick leave specific for one business was an estimated $480 per employee, and about five days of sick leave per year could be attributed to low ventilation rates. When comparing low ventilation rate areas of the building to higher ventilation rate areas, the relative risk of short-term sick leave was 1.53 times greater in the low ventilation areas.

Work productivity has been associated with ventilation rates, a contributing factor to SBS, and there's a significant increase in production as ventilation rates increase, by 1.7% for every two-fold increase of ventilation rate.

Causes

It has been suggested that sick building syndrome could be caused by inadequate ventilation, chemical contaminants from indoor or outdoor sources, and biological contaminants. Many volatile organic compounds, which are considered chemical contaminants, can cause acute effects on the occupants of a building. "Bacteria, molds, pollen, and viruses are types of biological contaminants" and can all cause SBS. In addition, pollution from outdoors, such as motor vehicle exhaust, can contribute to SBS. ASHRAE has recognized that polluted urban air, designated within the United States Environmental Protection Agency (EPA)´s air quality ratings as unacceptable requires the installation of treatment such as filtration for which the HVAC practitioners generally apply carbon impregnated filters and their like.

In 1973, in response to the 1973 oil crisis and conservation concerns, ASHRAE Standards 62-73 and 62-81 reduced required ventilation from 10 CFM (4.76 L/S) per person to 5 CFM (2.37 L/S) per person, but this was found to be a contributing factor to sick building syndrome. As of the 2016 revision, ASHRAE ventilation standards call for 5 to 10 CFM of ventilation per occupant (depending on the occupancy type) in addition to ventilation based on the zone floor area delivered to the breathing zone.

Prevention

  • toxin-absorbing plants, such as sansevieria.
  • Roof shingle non-pressure cleaning for removal of algae, mold, and Gloeocapsa magma.
  • Using ozone to eliminate the many sources, such as VOC, molds, mildews, bacteria, viruses, and even odors however numerous studies identify High-ozone shock treatment as ineffective despite commercial popularity and popular belief.
  • Replacement of water-stained ceiling tiles and carpeting.
  • Use of paints, adhesives, solvents, and pesticides in well-ventilated areas and use of these pollutant sources during periods of non-occupancy.
  • Increasing the number of air exchanges; the American Society of Heating, Refrigeration and Air-Conditioning Engineers recommend a minimum of 8.4 air exchanges per 24-hour period.
  • Proper and frequent maintenance of HVAC systems.
  • UV-C light in the HVAC plenum.
  • Installation of HVAC Air Cleaning systems or devices to remove VOC's, bioeffluents (people odors) from HVAC systems conditioned air.
  • Regular vacuuming with a HEPA filter vacuum cleaner to collect and retain 99.97% of particles down to and including 0.3 micrometers.
  • Increased ventilation rates that are above the minimum guidelines.
  • Lighting in the workplace should be designed to give individuals control, and be natural when possible.
  • There might be a gender difference in reporting rates of sick building syndrome because women tend to report more symptoms than men do. Along with this, some studies have found that women have a more responsive immune system and are more prone to mucosal dryness and facial erythema. Also, women are alleged by some to be more exposed to indoor environmental factors because they have a greater tendency to have clerical jobs, wherein they are exposed to unique office equipment and materials (example: blueprint machines), whereas men often have jobs based outside of offices.

    History

    In the late 1970s, it was noted that nonspecific symptoms were reported by tenants in newly constructed homes, offices, and nurseries. In media it was called "office illness". The term "Sick Building Syndrome" was coined by the WHO in 1986, when they also estimated that 10-30% of newly built office buildings in the West had indoor air problems. Early Danish and British studies reported symptoms.

    Poor indoor environments attracted attention. The Swedish allergy study (SOU 1989:76) designated "sick building" as a cause of the allergy epidemic as was feared. In the 1990s, therefore, extensive research into "sick building" was carried out. Various physical and chemical factors in the buildings were examined on a broad front.

    The problem was highlighted increasingly in media and was described as a "ticking time bomb". Many studies were performed in individual buildings.

    In the 1990s "sick buildings" were contrasted against "healthy buildings". The chemical contents of building materials was highlighted. Many building material manufacturers were actively working to gain control of the chemical content and to replace criticized additives. The ventilation industry advocated above all more well-functioning ventilation. Others perceived ecological construction, natural materials, and simple techniques as a solution.

    At the end of the 1990s came an increased distrust of the concept of "sick building". A dissertation at the Karolinska Institutet in Stockholm 1999 questioned the methodology of previous research, and a Danish study from 2005 showed these flaws experimentally. It was suggested that sick building syndrome was not really a coherent syndrome and was not a disease to be individually diagnosed. In 2006 the Swedish National Board of Health and Welfare recommended in the medical journal Läkartidningen that "sick building syndrome" should not be used as a clinical diagnosis. Thereafter, it has become increasingly less common to use terms such as "sick buildings" and "sick building syndrome" in research. However, the concept remains alive in popular culture and is used to designate the set of symptoms related to poor home or work environment engineering. "Sick building" is therefore an expression used especially in the context of workplace health.

    Sick building syndrome made a rapid journey from media to courtroom where professional engineers and architects became named defendants and were represented by their respective professional practice insurers. Proceedings invariably relied on expert witnesses, medical and technical experts along with building managers, contractors and manufacturers of finishes and furnishings, testifying as to cause and effect. Most of these actions resulted in sealed settlement agreements, none of these being dramatic. The insurers needed a defense based upon Standards of Professional Practice to meet a court decision that declared—that in a modern, essentially sealed building, the HVAC systems must produce breathing air for suitable human consumption. ASHRAE (American Society of Heating, Refrigeration and Air Conditioning Engineers, currently with over 50,000 international members) undertook the task of codifying its IAQ (Indoor Air Quality) standard.

    ASHRAE empirical research determined that "acceptability" was a function of outdoor (fresh air) ventilation rate and used carbon dioxide as an accurate measurement of occupant presence and activity. Building odors and contaminants would be suitably controlled by this dilution methodology. ASHRAE codified a level of 1,000 ppm of carbon dioxide and specified the use of widely available sense-and-control equipment to assure compliance. The 1989 issue of ASHRAE 62.1-1989 published the whys and wherefores and overrode the 1981 requirements that were aimed at a ventilation level of 5,000 ppm of carbon dioxide, (the OAHA workplace limit), federally set to minimize HVAC system energy consumption. This apparently ended the SBS epidemic.

    Over time, building materials changed with respect to emissions potential. Smoking vanished and dramatic improvements in ambient air quality, coupled with code compliant ventilation and maintenance, per ASHRAE standards have all contributed to the acceptability of the indoor air environment. With the publication of ASHRAE 62.1-2013 ASHRAE has reactivated 1981 with respect to ventilation rates. Only time and the courts will tell how right, or wrong ASHRAE is.

    While sick building syndrome (SBS) encompasses a multitude of non-specific symptoms, building-related illness (BRI) comprises specific, diagnosable symptoms caused by certain etiological agents (chemicals, bacteria, fungi, etc.). For instance, Legionnaire's disease, usually caused by Legionella pneumophila, involves a specific organism which could be ascertained through clinical findings as the source of contamination within a building. SBS does not have any known cure; alleviation consists of removing the affected person from the building associated with non-specific symptoms. BRI, on the other hand, utilizes treatment appropriate for the contaminant identified within the building (e.g., antibiotics for Legionnaire's disease). In most cases, simply improving the indoor air quality (IAQ) of a particular building will attenuate, or even eliminate, the acute symptoms of SBS, while removal of the source contaminant would prove more effective for a specific illness, as in the case of BRI.

    References

    Sick building syndrome Wikipedia